Low Frequency Online Ups For Industrial
- Andespower or OEM brand
- Foshan, China
- 15-20 working day
- 100units
- 1pc
Low Frequency Online Ups For Industrial
G series Online low Frequency UPS three phases in three phases out. A Digital Signal Processor(DSP) technology digitizes the data and mathematically manipulates them to provide an improved solution with high performance.
It is widely used for industrial, power distribution room, machine room, medical facility etc...
Low Frequency Online Ups For Industrial
Feature:
Online double-conversion
DSP technology guarantees hligh reliability
True galvanic isolation transformer disign
Control designed to withstand all kinds of loads.
Intelligent battery management to prolong battery lifecycle
Independent ventilation enhance durable operation under harsh environment
Varieties of communication options available
Specification:
MODEL | G10K | G15K | G20K | G30K | G40K | G60K | G80K | G100K | G120K | G160K | G200K | ||
CAPACITY | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/ 24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | 100KVA/ 80KW | 120KVA/ 96KW | 160KVA/128KW | 200KVA/160KW | ||
Dimensions, D x W x H(mm) | 656 x 405 x 817 | 656 x 405 x 941 | 821 x 432 x 1159 | 975 x 554 x 1286 | 975 x 554 x 1326 | 1051x705x1376 | |||||||
Net Weight(Kgs) | 114 | 127 | 142 | 211 | 259 | 293 | 403 | 464 | 558 | 707 | 708 | ||
INPUT | |||||||||||||
Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | ||||||||||||
Voltage Range | 285VAC ~ 475VAC | ||||||||||||
Frequency | 50/60 Hz ± 10% | ||||||||||||
OUTPUT | |||||||||||||
Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | ||||||||||||
Precision | Stationary: ±1% Transitory : ±5% (load variations 100-0-100%) | ||||||||||||
Frequency | 50/60 Hz synchronized ±1 % With mains absent ±0.1 Hz | ||||||||||||
Max. Synchronization speed | ±1 Hz/s | ||||||||||||
Waveform | Pure Sinewave | ||||||||||||
Total Harmonic Distortion(THDv) | <2% (Linear Load <5% (Non-linear load ) | ||||||||||||
Phase Displacement | 120º ±1% (balanced load ) 120º ±2% (imbalances 50% of the load) | ||||||||||||
Dynamic Recovery Time | <60ms at 90% of the static value | ||||||||||||
Admissible overload | 110% ~ 150% 10min~1min; 150% ~ >160% 1min~200ms; 200ms for >160% | ||||||||||||
Admissible Crest Factor | 3:1 | ||||||||||||
Admissible Power Factor | 0.6~1 (inductive or capacitive) | ||||||||||||
Imbalance Output Voltage @ 100% Unbalanced Load | <1% | ||||||||||||
Current Limit | High overload, short circuit, RMS Voltage Limit, High Crest Factor current, Peak Voltage Limit. | ||||||||||||
STATIC BYPASS | |||||||||||||
Type | Solid state | ||||||||||||
Voltage | 3 x 380VAC/400VAC (3Ph + N) | ||||||||||||
Frequency | 50/60 Hz | ||||||||||||
Activation Criterion | Microprocessor control | ||||||||||||
Transfer Time | zero | ||||||||||||
Admissible overload | 150% ~ 180% 1h~30s; 180% ~ >200% 30s~200ms; 200ms for >200% | ||||||||||||
Transfer to Bypass | Immediate, for overload above 160% | ||||||||||||
Retransfer | Automatic after alarm clear | ||||||||||||
MAINTENANCE BYPASS | |||||||||||||
Type | Without interruption | ||||||||||||
Voltage | 3 x 400V (3Ph + N) | ||||||||||||
Frequency | 50/60 Hz | ||||||||||||
BATTERY & CHARGER | |||||||||||||
Battery Type and Numbers(12V) | 29/30/31/32 (adjustable) | ||||||||||||
Rated voltage | 384VDC(32adjustable) | ||||||||||||
Charging Method | CC/CV | ||||||||||||
Charging Current | Default 10A, Max. = Capacity/Battery Voltage | Default: 10A, Max. 40A |